Weil-McLain · Boiler troubleshooting
Reducing vent and air length for elbows
What is going on
Each elbow beyond the allowed count reduces the maximum length. The allowed count is more than two elbows in the vent and one elbow in the air piping. Reduction applies to 45 and 90 degree elbows alike.
Likely causes
- Short-radius elbows add pressure loss and reduce allowable piping length
Check in this order
- Count all elbows in the vent piping, terminations and air piping.
- If there are more than two elbows in the vent or one in the air piping, cut the maximum length for each extra elbow.
- Reduce length by 15 ft per extra elbow for polypropylene 8-inch or 10-inch.
- Reduce length by 7 ft per extra elbow for PVC 8-inch.
- Reduce length by 15 ft per extra elbow for PVC 10-inch.
- If the pipe maker's equivalent length for an elbow is longer than these values, use the pipe maker's value instead.
- Use sweep elbows wherever possible.
Applies to: Vent and air piping with added elbows
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 Boiler Manual, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.