Viessmann · Boiler troubleshooting
Check boiler, DHW tank or supply/low-loss header temperature sensor
What is going on
Test the NTC 10 kΩ sensors by measuring resistance and comparing it with the sensor curve. Drain the boiler before replacing the boiler temperature sensor, because it sits in the heating water and can scald.
Likely causes
- Sensor reading deviates severely from the curve
Check in this order
- Boiler temperature sensor remove the lead and measure the resistance.
- DHW tank sensor pull the plug from the cable harness at the control unit and measure the resistance.
- Supply or low-loss header sensor pull plug X3 from the control unit and measure across terminals X3.4 and X3.5. Only one of these sensors may be used.
- Compare the measured values with the sensor curve.
- Replace the sensor if the deviation is severe.
Applies to: Boiler temperature sensor, DHW tank temperature sensor, supply temperature sensor, low-loss header temperature sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.