Weil-McLain · Boiler troubleshooting
Hydrostatic pressure test before connecting gas or electric
What is going on
Pressure test the boiler water side before the water piping, gas and electrical supply are permanently attached. Fill with water through a temporary supply tee and drain valve, and hold test pressure for 10 minutes.
Check in this order
- Pipe the supply tee and 3/4 in. elbow to the boiler supply connection. Use pipe dope sparingly. Tee sizes depend on model: 1x1x1/4 and 1x1x3/4 in. for Ultra-80 to -230, 1-1/4x1-1/4x1/4 and 1-1/4x1-1/4x3/4 in. for Ultra-299 and -399.
- Temporarily plug the 3/4 in. relief valve tapping in the street elbow with a 3/4 in. NPT plug.
- Connect a hose from a fresh water supply to the boiler drain valve. Make sure the hose can also drain the boiler after the test.
- Add a nipple and shutoff valve on the system supply connection to bleed air during fill. Add a shutoff valve on the system return connection. These valves are not supplied with the boiler.
- Open the shutoff valves, then slowly open the drain valve and water supply to fill the boiler. Close the drain valve when water reaches the shutoff valves, then close the shutoff valves.
- Slowly reopen the drain valve until the gauge reads at least 45 psig but no more than 55 psig.
- Hold test pressure for 10 minutes. Stay with the boiler during the test.
- Check that the gauge held steady and look for leaks. Repair any leak at once.
- Drain through the drain valve, disconnect the hose, remove the nipples and valves not used in the final piping, and remove the plug from the relief valve street elbow.
Applies to: All Ultra Series 4 models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.