Viessmann · Boiler troubleshooting
Remove the burner (CI2 399 to 2000)
What is going on
Burner removal for service. Burner weights: 399/500 MBH 25 lb (11.3 kg); 750/1000 MBH 35.5 lb (16.1 kg).
Check in this order
- Prepare the system for servicing per the burner/combustion chamber preparation chapter (page 20).
- Disconnect the burner gas line.
- Disconnect the cable to the burner control unit (BCU).
- If present, remove the combustion air intake hose; on CI2 1500 to 2000 remove the burner venturi and set it aside.
- Remove the 4 burner mounting bolts per burner and remove the burner.
- Rotate the burner and hook it into the burner maintenance bracket.
- Do not damage the burner gauze assembly mesh.
- Check the burner gasket on removal and replace if damaged.
Applies to: Vitocrossal 200 CI2 399 to 2000 MBH
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 27-28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.