Weil-McLain · Boiler troubleshooting

Read the lockout history

SVF Series 1

What is going on

The control stores the last three lockouts with the fault name, type, time, date, and the boiler status, temperatures, inputs and outputs at that time.

Check in this order

  1. Open DIAGNOSTICS and go to PAST ERRORS.
  2. Check CONTROL FAULTS, MANUAL RESET CNT and AUTO RESET CNT for the totals.
  3. Select LOCKOUT HISTORY 1 for the most recent error, then 2 and 3 for older ones.
  4. For each lockout, read FAULT NAME, FAULT TYPE, TIME and DATE.
  5. Open the Status, Temperatures, Inputs and Outputs screens to see conditions at the time of the lockout.

Applies to: Lockout review

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 82-83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.