Boiler water too hot in transitional seasons but fine in cold weather

Vitotronic 300

What is going on

The heating curve is too steep for mild weather. Adjust the curve so the boiler water temperature drops in spring and autumn while the cold-season performance stays the same.

Likely causes

  • Heating curve slope set too high for transitional times of year

Check in this order

  1. Open the hinged cover on the programming unit.
  2. Raise the slope of the heating curve by one increment.
  3. Lower the shift by about -3 °C (-5 °F).
  4. Check the room temperature and boiler water temperature at transitional and cold outdoor conditions.

Applies to: Heating curve slope and shift

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 operating instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.