Navien · Boiler troubleshooting

Non-direct (single pipe) venting setup

NCB700

What is going on

Single pipe operation draws combustion air from the room. Negative pressure can back-draft cold air and freeze the heat exchanger, and freeze damage from back-drafting is not covered by warranty. Use direct venting if back-drafting is possible.

Likely causes

  • Negative pressure in the installation space
  • Poor balance of the building air supply

Check in this order

  1. Insert the termination end cap into the intake air duct.
  2. Do not glue the end cap so it can be removed for cleaning.
  3. Provide two combustion air openings sized per the free-area table for the model.
  4. Maintain the non-direct vent clearances for the local code.
  5. If there is any doubt about back-drafting, use direct venting instead.

Applies to: NCB700 models using single pipe venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation manual, p. 66-67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.