Non-direct (single pipe) venting setup
What is going on
Single pipe operation draws combustion air from the room. Negative pressure can back-draft cold air and freeze the heat exchanger, and freeze damage from back-drafting is not covered by warranty. Use direct venting if back-drafting is possible.
Likely causes
- Negative pressure in the installation space
- Poor balance of the building air supply
Check in this order
- Insert the termination end cap into the intake air duct.
- Do not glue the end cap so it can be removed for cleaning.
- Provide two combustion air openings sized per the free-area table for the model.
- Maintain the non-direct vent clearances for the local code.
- If there is any doubt about back-drafting, use direct venting instead.
Applies to: NCB700 models using single pipe venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation manual, p. 66-67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.