Viessmann · Boiler troubleshooting

Outside temperature sensor installation

Vitotronic 300-K

What is going on

Mount the outside sensor where it reads true outdoor air. Keep it away from windows, doors and vents, and never cover it.

Check in this order

  1. Mount on a north or north-west wall, 6.6 to 8.2 ft (2 to 2.5 m) above ground level.
  2. In multistorey buildings, mount in the upper half of the second floor.
  3. Do not mount above windows, doors or ventilation outlets.
  4. Do not mount immediately below balconies or gutters.
  5. Do not cover the sensor.
  6. Connect with two-wire communication cable, AWG 18, maximum 120 ft (35 m).

Applies to: Outside temperature sensor on Vitotronic 300-K

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.