Weil-McLain · Boiler troubleshooting
Lockout on the manual reset high temperature limit
What is going on
If boiler outlet water goes over the Manual Reset High Temp Limit setting (200°F from the factory), the control shuts the boiler down and locks out. It needs a manual reset. Weil-McLain does not recommend changing this setting.
Likely causes
- Boiler outlet water went over the limit setting
- Limit setting was lowered from the 200°F default
Check in this order
- Check the setting contractor menu > Boiler Settings > Manual Reset High Temp Limit.
- Look at Boiler Out / Boiler In and Target Temp on the boiler information screen.
- Check the target temperatures of each priority. System presets top out at 180°F max target (120°F for slab on grade).
- If the system mixes low-temperature circuits (radiant slab) with high-temperature ones, those low circuits need their own limit wired to an external limit input.
- Reset at the display. If it keeps tripping, go to the ECO Tec Boiler Manual troubleshooting section.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Wizard screen, p.29; Boiler Settings, p.58; Figure 25 System Type Presets, p.54; Temperature settings note, p.2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.