Viessmann · Boiler troubleshooting
Check the rotary damper setting
What is going on
Check the damper position at standstill and during start-up. Factory settings must not be changed.
Likely causes
- Compensating tube not connected between gas valve and Venturi mixing pipe
Check in this order
- Open the gas shut-off valve.
- With the burner off, check that the rotary damper windows are fully open and the scale ring reads 0 against the marking on the air damper actuator.
- Check that the compensating tube is connected between the gas valve and the Venturi mixing pipe.
- Start the burner.
- During start-up, check that the windows nearly close for about 5 seconds and that the scale ring matches the damper setting table.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.