Viessmann · Boiler troubleshooting

Check the rotary damper setting

Vitocrossal 300 CA3B Dual Fuel

What is going on

Check the damper position at standstill and during start-up. Factory settings must not be changed.

Likely causes

  • Compensating tube not connected between gas valve and Venturi mixing pipe

Check in this order

  1. Open the gas shut-off valve.
  2. With the burner off, check that the rotary damper windows are fully open and the scale ring reads 0 against the marking on the air damper actuator.
  3. Check that the compensating tube is connected between the gas valve and the Venturi mixing pipe.
  4. Start the burner.
  5. During start-up, check that the windows nearly close for about 5 seconds and that the scale ring matches the damper setting table.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.