Viessmann · Boiler troubleshooting

Mounting the front part of the control unit (VD2/VD2A/CT3)

Vitotronic 300 GW2

What is going on

Refit the front housing after wiring. Keep the flat cable and programming unit cable routed through the cable guides in the cover.

Check in this order

  1. Position the front housing and clip its hinges onto the counter-parts on the main housing.
  2. Release the stay bar, open the front up and lock the stay bar at point A.
  3. Insert the flat cable from the Optolink into plug X20.
  4. Insert the programming unit plug into socket X10 and route the cable through the cover guides.
  5. Engage the stay bar in the front housing.
  6. Close the front housing.
  7. Secure the front housing with the supplied screws.
  8. Install the connection enclosure cover and secure it with the supplied screw.

Applies to: Vitotronic 300 GW2 with VD2, VD2A or CT3 control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 57-58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.