Viessmann · Boiler troubleshooting

Replacing the burner control unit

Vitocrossal 300 CA3B Dual Fuel

What is going on

Burner control unit removal and installation.

Check in this order

  1. Disconnect KM-BUS connector avG.
  2. Undo the 2 mounting screws. Torque to 9 lb.in (1 Nm) on reinstall.
  3. Lift the display and programming unit and pull off the connector of the burner control unit connecting cable. Remove the display and programming unit.
  4. Remove all connecting cables from the burner control unit.
  5. Pull the coding card from the burner control unit.
  6. Undo the 4 mounting screws on the burner control unit.
  7. Remove the burner control unit.
  8. Install the new burner control unit in reverse order.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel CA3B service instructions, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.