Example C master boiler field wiring
What is going on
The master boiler takes 120 VAC power and the boiler circulator on the BOILER PUMP terminals and 2-pin plug at J4-4. Zone 1 and Zone 2 are wired to the master. System circulators 6a and 6b are driven through relays with a 120 V coil and NO contact, using G, W and B leads. Outdoor air, system supply and system return sensors go to J19.
Check in this order
- Connect 120 VAC power to L1 HOT, L1 NEUTRAL and L1 GROUND.
- Wire the boiler circulator to BOILER PUMP and the 2-pin plug at J4-4.
- Wire Circulator 1 and Circulator 2 to their outputs, rated 2.0 A max each.
- Wire the system circulator relays (6a and 6b) with 120 V coil and NO contact, using G, W and B leads.
- Wire the outdoor air, system supply and system return sensors to J19.
- Wire the Zone 1 and Zone 2 thermostats to their W, R and C terminals.
Applies to: Example C master boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.