Weil-McLain · Boiler troubleshooting

Example C master boiler field wiring

Evergreen Series 2

What is going on

The master boiler takes 120 VAC power and the boiler circulator on the BOILER PUMP terminals and 2-pin plug at J4-4. Zone 1 and Zone 2 are wired to the master. System circulators 6a and 6b are driven through relays with a 120 V coil and NO contact, using G, W and B leads. Outdoor air, system supply and system return sensors go to J19.

Check in this order

  1. Connect 120 VAC power to L1 HOT, L1 NEUTRAL and L1 GROUND.
  2. Wire the boiler circulator to BOILER PUMP and the 2-pin plug at J4-4.
  3. Wire Circulator 1 and Circulator 2 to their outputs, rated 2.0 A max each.
  4. Wire the system circulator relays (6a and 6b) with 120 V coil and NO contact, using G, W and B leads.
  5. Wire the outdoor air, system supply and system return sensors to J19.
  6. Wire the Zone 1 and Zone 2 thermostats to their W, R and C terminals.

Applies to: Example C master boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.