Viessmann · Boiler troubleshooting

Checking the fixed high limit (STB test)

Vitotronic 100 GC1

What is going on

Test the fixed high limit (STB) on the Vitotronic 100 with the TÜV test button held. The adjustable high limit is bypassed during the test, so the burner runs until the STB cuts it off.

Check in this order

  1. Make sure a minimum flow is present. Boiler flow should be about 10% of rated output.
  2. Reduce the heat demand as far as possible.
  3. Hold the TÜV test button down. The adjustable high limit R is now bypassed.
  4. Let the burner run until boiler water reaches the safety temperature and the fixed high limit (STB) switches off.
  5. Release the TÜV button. The display shows fault D4.
  6. Wait until boiler water is 15 to 20 °C (25 to 35 °F) below the set safety temperature.
  7. Press button E to reset the fixed high limit. Fault D4 clears from the display.

Applies to: Vitotronic 100, GC1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100/300-K installation and service manual, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.