Weil-McLain · Boiler troubleshooting

Chimney and vent requirements

CGi Series 5

What is going on

Venting must follow Part 7 of the National Fuel Gas Code and local building codes. A chimney or vent without a listed cap must extend at least 3 feet above the roof penetration and at least 2 feet higher than any building part within 10 feet horizontally. A lined chimney is preferred and required where codes call for it. Cold masonry chimneys can suffer condensation damage with atmospheric boilers. Where two or more gas appliances share a chimney, the combined area should be at least the largest outlet plus 50 percent of each additional outlet. Minimum vent sizes are on the Ratings table (p. 91).

Likely causes

  • Condensation damaging a cold masonry chimney

Check in this order

  1. Confirm the vent or chimney extends at least 3 feet above the roof and 2 feet above any building within 10 feet.
  2. Inspect the existing chimney or tile liner for cracks and damage before install. Replace perforated or damaged liners.
  3. On a cold masonry chimney, line it with corrosion-resistant metal such as AL29-4C single-wall stainless or a properly sized B-vent liner.
  4. Provide a drain trap to remove condensate.
  5. Size a shared chimney using the largest outlet plus 50 percent of each additional outlet area.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.