Weil-McLain · Boiler troubleshooting
Chimney and vent requirements
What is going on
Venting must follow Part 7 of the National Fuel Gas Code and local building codes. A chimney or vent without a listed cap must extend at least 3 feet above the roof penetration and at least 2 feet higher than any building part within 10 feet horizontally. A lined chimney is preferred and required where codes call for it. Cold masonry chimneys can suffer condensation damage with atmospheric boilers. Where two or more gas appliances share a chimney, the combined area should be at least the largest outlet plus 50 percent of each additional outlet. Minimum vent sizes are on the Ratings table (p. 91).
Likely causes
- Condensation damaging a cold masonry chimney
Check in this order
- Confirm the vent or chimney extends at least 3 feet above the roof and 2 feet above any building within 10 feet.
- Inspect the existing chimney or tile liner for cracks and damage before install. Replace perforated or damaged liners.
- On a cold masonry chimney, line it with corrosion-resistant metal such as AL29-4C single-wall stainless or a properly sized B-vent liner.
- Provide a drain trap to remove condensate.
- Size a shared chimney using the largest outlet plus 50 percent of each additional outlet area.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 Gas-Fired Water Boiler Manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.