Viessmann · Boiler troubleshooting
Check CO2 and O2 at low and high fire
What is going on
Run the boiler in actuator test at low fire and high fire and check the combustion readings at each.
Likely causes
- Combustion readings outside the allowed range
Check in this order
- Connect the flue gas analyzer to the test port at the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Enter the service menu and select the actuator test.
- For low fire, select Base load OFF so Base load ON appears. Measure CO2 and O2.
- Select 'all actuators off' to end low fire.
- For high fire, select Full load OFF so Full load ON appears. Measure CO2 and O2.
- Exit the actuator test and record both readings on page 101.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 30-31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.