Viessmann · Boiler troubleshooting
Check tank, supply or low loss header temperature sensor
What is going on
Resistance check of the NTC 10 kOhm tank, supply or low loss header sensor.
Likely causes
- Faulty sensor (resistance deviates more than 10%)
Check in this order
- Disconnect plug TS1 or the sensor from the electronics module.
- Measure the sensor resistance.
- Compare it with the NTC curve.
- If the deviation is more than 10%, replace the sensor.
Applies to: Vitocrossal 200 CI2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.