Viessmann · Boiler troubleshooting
Cascade control: set supply temperature and control types
What is going on
The cascade regulates the supply temperature by starting or stopping burners or burner stages. The set supply temperature comes from the heating circuits, DHW demand and external demands such as coding 9b or the 0 to 10 V Input Module. Control types: stand-alone (parallel or series boiler arrangement, coding 3b 0 to 3) and sequential (coding 3b: 4), where the lead boiler can modulate and the others run in two stages.
Check in this order
- Parallel stand-alone coding 3b 0 without supply sensor, or 1 with supply sensor.
- Series stand-alone coding 3b 2 without supply sensor, or 3 with supply sensor.
- Sequential coding 3b 4.
- With a supply sensor, start-up and shutdown use the supply temperature deviation. Without it, they use the boiler water temperature and estimated average boiler temperature, counting only boilers whose isolation valve is open.
Applies to: Vitocontrol-S VD2/CT3/CM2 cascade
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 124-125. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.