Weil-McLain · Boiler troubleshooting
Check piping, air openings and venting
What is going on
Leaks, blocked air openings and damaged venting all cause safety and reliability problems.
Likely causes
- Make-up water from leaks shortens boiler life. Minerals build up and cause heat exchanger overheating and failure.
Check in this order
- Check all water and gas piping for leaks and fix any found.
- Check the gas line using the procedure on page 48.
- Confirm combustion and ventilation air openings to the boiler room or building are open and clear. Check any automatic combustion air dampers for operation and wiring.
- Confirm the boiler vent discharge and air intake are clean and unobstructed.
- Visually inspect the full flue system and any air piping for blockage, deterioration or leakage.
- Repair leaking joints per the vent manufacturer's instructions.
- If air is ducted to the boiler, confirm the air inlet pipe is connected and sealed.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 92. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.