Chilled water system piping (boiler in parallel with chiller)

SlimFit Series 2

What is going on

The chiller is piped in parallel with the boiler. Valves keep chilled medium out of the boiler.

Likely causes

  • Chilled medium entering the boiler
  • Gravity circulation through the boiler during cooling
  • Wrong antifreeze in the boiler loop

Check in this order

  1. Pipe the chiller in parallel with the boiler.
  2. Install valves that stop chilled medium from entering the boiler.
  3. If coils in air handlers can see refrigerated air, add flow control valves or other automatic means to stop gravity circulation during cooling.
  4. Install a closed-type expansion tank for this system (Figure 20, item 15).
  5. Install a union on the boiler supply and return connections close to the boiler for service.
  6. Use only antifreeze listed by Weil-McLain for this boiler (see page 105). Consider antifreeze effects on circulator sizing and DHW performance.
  7. Check local codes, which may require a double-wall DHW heat exchanger.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.