Viessmann · Boiler troubleshooting

Check the room temperature sensor (Part No. 7133 379)

Vitocontrol-S VD2/CT3/CM2

What is going on

Test the room sensor resistance and compare it with the room temperature shown on the control.

Check in this order

  1. Disconnect the wires from the sensor.
  2. Measure the sensor resistance at terminals 9 and 13b.
  3. Compare the reading with the resistance table for the room temperature.
  4. Compare the resistance-based temperature with the actual room temperature shown on the display (scan on page 109).
  5. Check the installation first. Replace the sensor if the deviation is severe.

Applies to: Room temperature sensor, Part No. 7133 379

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 152. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.