System Layout 8: DHW with low-loss header and three zone circuits

Vitodens 200-W

What is going on

Vitodens 200-W B2HA/B2HB with DHW storage tank, low-loss header and three zone circuits controlled by thermostats (dry contact). Zones 2 and 3 use an AM1 extension module (accessory).

Check in this order

  1. Install a low-loss header (strongly recommended).
  2. Connect the DHW pump to output 21 and the boiler pump to output 20.
  3. Wire zone circuit 1 to output 157.
  4. Wire zone circuit 2 to output A1 and zone circuit 3 to output A2 on the AM1 extension module.
  5. Connect the thermostats for zones 1, 2 and 3 as dry contacts.
  6. Install the outdoor temperature sensor, DHW sensor and supply temperature sensor.

Applies to: Vitodens 200-W B2HA/B2HB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.