Check blower speeds
What is going on
Compare blower RPM at each firing rate with the blower speed table (Figure 79, page 88).
Check in this order
- For altitude above 5,500 ft, enable high altitude in the boiler setup menu. Below 5,500 ft, do NOT enable it.
- Open Manual test mode on the control display (see page 80).
- Set the firing rate to Low. Record the blower RPM and compare with Figure 79.
- Set the firing rate to MEDIUM (ignition rate). RPM should be within 200 RPM of the table value.
- Set the firing rate to High. RPM should be within 200 RPM of the table value.
- If any value is out of range, contact the factory for technical help.
Applies to: SVF 1500-3000 Series 1 boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF Series 1 boiler manual, p. 98. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.