Weil-McLain · Boiler troubleshooting
Gas valve adjustment at high fire
What is going on
Only a qualified technician with calibrated combustion instruments should adjust the valve.
Likely causes
- Difficulty igniting
- Poor flame stability at low fire
- Combustion noise
- High carbon monoxide
Check in this order
- Set MAX RATE and MIN RATE for the priority being tested to 100% and 10%.
- Go to DIAGNOSTICS, Manual test mode, and force HIGH fire.
- Confirm blower speed reaches the RPM in Figure 125, 126 or 127.
- Read CO2 and CO and allow the analyzer to stabilize.
- If CO2 is high, turn the throttle screw clockwise in small steps.
- If CO2 is low, turn the throttle screw counter-clockwise in small steps.
- Continue until the target CO2 is reached and confirm CO is within limits.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 135-136. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.