Weil-McLain · Boiler troubleshooting

Gas valve adjustment at high fire

ECO Tec Series 3

What is going on

Only a qualified technician with calibrated combustion instruments should adjust the valve.

Likely causes

  • Difficulty igniting
  • Poor flame stability at low fire
  • Combustion noise
  • High carbon monoxide

Check in this order

  1. Set MAX RATE and MIN RATE for the priority being tested to 100% and 10%.
  2. Go to DIAGNOSTICS, Manual test mode, and force HIGH fire.
  3. Confirm blower speed reaches the RPM in Figure 125, 126 or 127.
  4. Read CO2 and CO and allow the analyzer to stabilize.
  5. If CO2 is high, turn the throttle screw clockwise in small steps.
  6. If CO2 is low, turn the throttle screw counter-clockwise in small steps.
  7. Continue until the target CO2 is reached and confirm CO is within limits.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 135-136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.