Installing the KM-BUS Expansion Module

KM-BUS Expansion Module

What is going on

Mount the module near the boiler, connect the accessories, and link the module to the Vitotronic control unit.

Check in this order

  1. Open the KM-BUS Expansion Module.
  2. Mount the base on the wall with the screws and wall anchors supplied. Install it near the boiler because of the length of the KM-BUS connecting cable.
  3. Connect accessories to terminals "1" and "2" on the plug, or to terminal strip "X8" on the module.
  4. Connect the plug to the module circuit board in sockets X1 to X7.
  5. Insert the plug of the module's connecting cable into socket "145" on the control unit and apply strain relief.
  6. Check all connections against the Electrical Connections diagram before closing the module.

Applies to: Up to 9 KM-BUS devices (mixing valve actuator kits, Vitotrol, Switching Module-V) on a Vitotronic control, which is the only control series this module is for.

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KM-BUS Expansion Module installation instructions, p. 1-2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.