Weil-McLain · Boiler troubleshooting
WMZV zone valve zone controller plus DHW (DHW piped to boiler)
What is going on
Input 2 takes the space heating call from the zone controller. The system circulator on Output 2 runs on any space heating call. DHW is on Input 1 at Priority 1.
Check in this order
- Wire the zone controller call (X-X) to Input 2 and keep Input 2 on Priority 2.
- Set Priority 2 for the space heating system type.
- Wire the system circulator to Output 2.
- Wire the DHW aquastat to Input 1, assign Input 1 to Priority 1, and wire the DHW circulator to Output 1.
- Use the factory DHW settings or change them as needed.
Applies to: SVF Series 1 with WMZV zone valve controller
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.