Weil-McLain · Boiler troubleshooting

WMZV zone valve zone controller plus DHW (DHW piped to boiler)

SVF Series 1

What is going on

Input 2 takes the space heating call from the zone controller. The system circulator on Output 2 runs on any space heating call. DHW is on Input 1 at Priority 1.

Check in this order

  1. Wire the zone controller call (X-X) to Input 2 and keep Input 2 on Priority 2.
  2. Set Priority 2 for the space heating system type.
  3. Wire the system circulator to Output 2.
  4. Wire the DHW aquastat to Input 1, assign Input 1 to Priority 1, and wire the DHW circulator to Output 1.
  5. Use the factory DHW settings or change them as needed.

Applies to: SVF Series 1 with WMZV zone valve controller

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.