Remote target setup with 0-10VDC input
What is going on
A 0-10VDC signal adjusts the supply target temperature. It replaces the outdoor sensor as the target modifier. The control does not control the target itself.
Check in this order
- Wire the 0-10VDC positive signal to J16 terminal 6 and the common to terminal 5.
- Wire a heat demand dry contact to an unused input and its pump or valve to the matching output.
- Assign and set up a priority for that input in the Wizard or the contractor menu.
- Set TARGET ADJUST to 0-10V for the priority used for space heating (Priority 2 or 3).
- Set VOLTS FOR MAX TARGET and MAX TARGET TEMP at the voltage that calls for the highest target.
- Set VOLTS FOR MIN TARGET and MIN TARGET TEMP at the voltage that calls for the lowest target.
- Between the two voltages, the target temperature scales in proportion between MAX and MIN TARGET TEMP.
- A dry contact heat demand must be present to start a call for heat.
Applies to: Evergreen 110/155/220/299/300/399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.