Weil-McLain · Boiler troubleshooting

Remote target setup with 0-10VDC input

Evergreen Series 2

What is going on

A 0-10VDC signal adjusts the supply target temperature. It replaces the outdoor sensor as the target modifier. The control does not control the target itself.

Check in this order

  1. Wire the 0-10VDC positive signal to J16 terminal 6 and the common to terminal 5.
  2. Wire a heat demand dry contact to an unused input and its pump or valve to the matching output.
  3. Assign and set up a priority for that input in the Wizard or the contractor menu.
  4. Set TARGET ADJUST to 0-10V for the priority used for space heating (Priority 2 or 3).
  5. Set VOLTS FOR MAX TARGET and MAX TARGET TEMP at the voltage that calls for the highest target.
  6. Set VOLTS FOR MIN TARGET and MIN TARGET TEMP at the voltage that calls for the lowest target.
  7. Between the two voltages, the target temperature scales in proportion between MAX and MIN TARGET TEMP.
  8. A dry contact heat demand must be present to start a call for heat.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.