Weil-McLain · Boiler troubleshooting
Proof of closure interlock (flow switch or combustion air damper)
What is going on
A flow switch or combustion air damper (CAD) end switch can be wired as a proof-of-closure interlock. Doing so requires removing the factory jumper on connector J18. No control settings are needed for a flow switch. For a CAD interlock, the control should be set up so the damper opens whenever the boiler is called to fire.
Check in this order
- Remove the jumper on connector J18 before wiring the external device.
- Wire the flow switch or CAD end switch to J18 as shown in the wiring diagram (Figure 76, page 78).
- For a CAD interlock, assign INPUT 3 as an AUX PUMP/OUTPUT function.
- Set the AUX PUMP/OUTPUT operating mode to local or System Damper so the damper runs on every call to fire.
- Wire the CAD motor to OUTPUT 3 (120VAC). If the damper motor needs another voltage or more current than the output allows, use an isolation relay.
- On multi-boiler installs, wire all proof-of-closure inputs in series with the end point devices and each boiler's closure switch input.
- Use only isolated dry contacts, because the J18 circuit carries 5 VDC.
Applies to: ECO Tec Series 3 80/110/150/199 (Combi and Heating Only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.