Viessmann · Boiler troubleshooting
Return valve control for return temperature (circuit diagram 4)
What is going on
Return valve method for systems with no way to change the downstream heating circuits, such as older systems.
Likely causes
- Return temperature falls below the required minimum value
Check in this order
- Check that sensor T2 switches the shunt pump on when the return is low.
- If the minimum return temperature is still not reached, check that the return valve closes proportionally via sensor T1.
- Confirm coding 0C 1 is set for continuous return temperature control.
Applies to: Single-boiler system with shunt pump and return valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.