Check flame and combustion with instruments
What is going on
Measure combustion at the flue with a calibrated analyzer after the boiler is firing.
Check in this order
- Call for heat on one of the heat demand inputs.
- Hold the up and down arrow keys for seven seconds to open the contractor menus.
- Go to DIAGNOSTICS and select Manual Test Mode.
- Remove the flue temperature sensor and fit a 1/4 in BSP hose barb and hose.
- Insert the combustion probe and test for CO2 (or O2) and CO.
- Compare results to the values in the CO2 tables (page 89).
- If results are not acceptable, follow the gas valve adjustment procedure.
- Re-install the flue temperature sensor before leaving. Leaving it out allows flue gas into the boiler room.
Applies to: SVF 1500-3000
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.