Weil-McLain · Boiler troubleshooting

Check flame and combustion with instruments

SVF Series 1

What is going on

Measure combustion at the flue with a calibrated analyzer after the boiler is firing.

Check in this order

  1. Call for heat on one of the heat demand inputs.
  2. Hold the up and down arrow keys for seven seconds to open the contractor menus.
  3. Go to DIAGNOSTICS and select Manual Test Mode.
  4. Remove the flue temperature sensor and fit a 1/4 in BSP hose barb and hose.
  5. Insert the combustion probe and test for CO2 (or O2) and CO.
  6. Compare results to the values in the CO2 tables (page 89).
  7. If results are not acceptable, follow the gas valve adjustment procedure.
  8. Re-install the flue temperature sensor before leaving. Leaving it out allows flue gas into the boiler room.

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.