Weil-McLain · Boiler troubleshooting

No display and boiler will not respond to call for heat (no 24 V)

SlimFit Series 2

What is going on

Display is blank and the boiler does not respond to a call for heat. The control is not getting 24 V power.

Likely causes

  • Short circuit or incorrect wiring
  • Blown 3-amp low voltage fuse on control
  • Failed transformer

Check in this order

  1. Check wiring for shorts or errors and correct per the wiring diagram, including transformer connection to the control.
  2. Check the 3-amp low voltage fuse on the control (see page 94) and replace with the proper part if blown.
  3. If the fuse blows again, recheck wiring per the diagram.
  4. Check for 24 VAC output at the transformer.
  5. Replace the transformer if it receives 120 VAC but outputs no 24 VAC.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.