Weil-McLain · Boiler troubleshooting
No display and boiler will not respond to call for heat (no 24 V)
What is going on
Display is blank and the boiler does not respond to a call for heat. The control is not getting 24 V power.
Likely causes
- Short circuit or incorrect wiring
- Blown 3-amp low voltage fuse on control
- Failed transformer
Check in this order
- Check wiring for shorts or errors and correct per the wiring diagram, including transformer connection to the control.
- Check the 3-amp low voltage fuse on the control (see page 94) and replace with the proper part if blown.
- If the fuse blows again, recheck wiring per the diagram.
- Check for 24 VAC output at the transformer.
- Replace the transformer if it receives 120 VAC but outputs no 24 VAC.
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.