Navien · Boiler troubleshooting
Measuring and adjusting inlet gas pressure
What is going on
Check inlet gas pressure during the commissioning run and adjust the regulator if needed.
Check in this order
- Shut off the manual gas valve.
- Remove the front cover (4 latches).
- Loosen the test screw and connect a manometer to the pressure port. Zero the manometer first.
- Re-open the manual gas valve and check for leaks.
- Open multiple high-flow fixtures such as tub and shower faucets to bring the boiler to maximum firing.
- Read the inlet pressure and compare with NG 3.5 to 10.5 in WC or LP 8.0 to 13.0 in WC.
- If out of range, adjust the gas regulator on the gas supply.
- Reinstall the front cover when finished.
Applies to: NFB-301C/399C
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NFB-C quick installation guide, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.