Viessmann · Boiler troubleshooting

Connect power supply

Vitocontrol-S VD2/CT3/CM2Vitotronic 100

What is going on

Supply is 120 VAC, 1 PH, 60 Hz. The control must be grounded.

Check in this order

  1. Make sure the main supply to the control has overcurrent protection of at least 6 A and a 2-pole disconnect.
  2. Provide disconnect means and overcurrent protection as per local codes.
  3. Connect the supply wire to terminals 11, N and G on the DIN rail in the connection enclosure.
  4. Do not interchange L, N and G.

Applies to: Control unit power supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.