Rinnai · Boiler troubleshooting
DHW temperature drops
What is going on
On the Rinnai E50CRN, E75CRN, E75CRP, E110CRN and E110CRP boilers, hot water starts out fine and then fades during a draw. What I usually find is crossed hot and cold connections or the wrong flow restrictor fitted at install, and after that a power setting someone left too low. A sensor or wiring fault is further down the list.
Likely causes
- Hot and cold connections swapped
- Wrong flow reducing valve for the model
- DHW power set too low
- T3 sensor or wiring fault
Check in this order
- Check the hot and cold connections at the boiler
- Check the restrictor type against the installation instructions
- Check PARA parameter 43
- Check DHW sensor T3 and its wiring, with power off when handling connectors
- Run a long draw and watch whether the temperature steadies once the settings are corrected
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.