Rinnai · Boiler troubleshooting
DHW temperature drops
What is going on
Hot water temperature falls during use.
Likely causes
- Hot and cold connections swapped
- Wrong flow reducing valve
- DHW power set too low
- T3 sensor or wiring fault
Check in this order
- Check connections.
- Check restrictor type against the installation instructions.
- Check PARA parameter 43.
- Check DHW sensor T3 and wiring.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.