Verify the remaining appliances on an old common vent

ECO Tec Series 3

What is going on

Check each appliance still on the old common vent by itself, with all others off, to confirm the vent can carry it safely.

Likely causes

  • Common vent may be oversized for the remaining appliances after the old boiler is removed.
  • Blocked, leaking, corroded or poorly pitched vent can cause spillage.

Check in this order

  1. Seal any unused openings in the common vent.
  2. Inspect the vent for correct size, horizontal pitch, blockage, restriction, leakage, corrosion or other defects.
  3. Close building doors and windows and doors to the spaces with appliances on the vent. Run clothes dryers and any non-vented appliance.
  4. Turn on exhaust fans such as range hoods and bathroom fans to maximum speed. Do not run a summer exhaust fan. Close fireplace dampers.
  5. Run the appliance being tested with the lighting instructions. Set its thermostat so it runs continuously.
  6. After 5 minutes of main burner operation, check for spillage at the draft hood relief opening with a match, candle or smoke.
  7. When the test passes, return doors, windows, fans, dampers and other gas appliances to their original state.

Applies to: Existing common vent after ECO Tec replacement

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.