No display and blower running at full speed
What is going on
Control is not getting 24 V power.
Likely causes
- Short circuit or incorrect wiring
- Blown 3 A low voltage fuse
- Transformer wiring wrong or transformer not outputting 24 VAC
Check in this order
- Check wiring for shorts or errors; correct it to the wiring diagram, including the transformer connection to the U-Control.
- Check the 3 A low voltage fuse (page 116) and replace it with the proper part if blown. If it blows again, recheck wiring.
- Check transformer output. If it receives 120 VAC but gives no 24 VAC, replace the transformer.
Applies to: Ultra 80, 105, 155, 230, 299, 399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 118. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.