No display and blower running at full speed

Ultra Series 4

What is going on

Control is not getting 24 V power.

Likely causes

  • Short circuit or incorrect wiring
  • Blown 3 A low voltage fuse
  • Transformer wiring wrong or transformer not outputting 24 VAC

Check in this order

  1. Check wiring for shorts or errors; correct it to the wiring diagram, including the transformer connection to the U-Control.
  2. Check the 3 A low voltage fuse (page 116) and replace it with the proper part if blown. If it blows again, recheck wiring.
  3. Check transformer output. If it receives 120 VAC but gives no 24 VAC, replace the transformer.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 118. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.