Reinstall cleanout plate and burner assembly
What is going on
Reinstall the cleanout plate with a new silicone cord gasket and torque the nuts correctly.
Check in this order
- Replace the red silicone cord gasket with a new one from the annual maintenance kit or cover plate kit; remove old silicone first.
- Seat the gasket in the groove starting at the upper corners, leaving slight slack, then the lower corners.
- Re-install the original cleanout plate gasket after inspection.
- Position the cleanout plate and install nuts in the staggered pattern.
- Tighten to 18 N-m / 160 in-lbs / 13 ft-lbs in top-to-bottom center-out sequence (Figure 95, page 104).
- Reinstall the burner, combustion chamber access plate, and blower/venturi/mixing tube assembly (see page 91).
- Reconnect wiring, including the igniter ground wire to the top igniter mounting screw.
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 103-104. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.