Carlin · Boiler troubleshooting

Moving a Carlin EZ burner to high biodiesel blends (above B20 / B100)

Carlin EZ

What is going on

Biodiesel cleans sludge out of the tank at first and lowers CO2. Set up before the fuel changes.

Likely causes

  • Sludge loosened from the tank plugging the filter or sticking the pump
  • Low CO2 after the switch
  • Older burner not converted for high blends

Check in this order

  1. Use a single-pipe system and a 10 micron spin-on filter (NORA recommendation). Change filters more often during the switch.
  2. Before going above B20, set CO2 at the high end (not below 11.5%). For WGO/WTGO/SGO going to B100 the supplement says set 12.25-12.5% CO2 on #2 oil first.
  3. Older Carlin burners need the field conversion (new head, higher pump pressure, B100 pump, other control settings) from Carlin's online OEM guide before running high blends.
  4. Use the B100 column settings in the boiler's burner table for nozzle, pump pressure, head bar and air band.

Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Biodiesel best practices, p.20; supplement table 1 note, p.1. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.