Moving a Carlin EZ burner to high biodiesel blends (above B20 / B100)
What is going on
Biodiesel cleans sludge out of the tank at first and lowers CO2. Set up before the fuel changes.
Likely causes
- Sludge loosened from the tank plugging the filter or sticking the pump
- Low CO2 after the switch
- Older burner not converted for high blends
Check in this order
- Use a single-pipe system and a 10 micron spin-on filter (NORA recommendation). Change filters more often during the switch.
- Before going above B20, set CO2 at the high end (not below 11.5%). For WGO/WTGO/SGO going to B100 the supplement says set 12.25-12.5% CO2 on #2 oil first.
- Older Carlin burners need the field conversion (new head, higher pump pressure, B100 pump, other control settings) from Carlin's online OEM guide before running high blends.
- Use the B100 column settings in the boiler's burner table for nozzle, pump pressure, head bar and air band.
Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Biodiesel best practices, p.20; supplement table 1 note, p.1. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.