Carlin · Boiler troubleshooting

Setting Carlin EZ combustion (inside air or ducted air)

Carlin EZ

What is going on

Target numbers depend on the incoming air temperature when the air is piped from outside.

Likely causes

  • CO2 drifts when the cover goes on or outside air temperature changes

Check in this order

  1. Run the burner at least 15 minutes, with the cover on if it has one, before final readings.
  2. Smoke must be zero. Set draft per the boiler (natural draft usually -0.01 to -0.02 in. w.c. over fire).
  3. Inside air aim for 12.0-12.5% CO2 (3.9-4.6% O2).
  4. Ducted air, measure the incoming air temperature: -20 to 0°F = 10.2-11.0% CO2; 5 to 30°F = 11.0-11.5%; 35 to 60°F = 11.5-12.2%; 65°F and up = 12.0-12.5%.
  5. Open the air band to lower CO2, close it to raise CO2. Tighten the clamp screw.
  6. Check the flame does not hit any surface. Recheck the install after 1-2 weeks of running.

Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Adjustment and verification, Table 5, p.15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.