Carlin EZ with CAP system shuts down or locks out (blocked air intake)

Carlin EZ

What is going on

The CAP system stops the burner when the outside combustion air pipe is blocked.

Likely causes

  • Snow, ice or a bird nest blocking the intake termination
  • Intake pipe too long (over 80 ft total, each elbow counts 10 ft) or wrong pipe
  • Missing bird screen / wrong termination

Check in this order

  1. The control checks the intake during pre-purge. Blocked = it will not try to light.
  2. If the intake blocks while running, the burner shuts off after 20 seconds of blockage.
  3. After a shutdown it recycles up to 3 times with a 1 minute wait. Still blocked on all 3 = lockout for that call for heat.
  4. Clear the termination. It should be a downward PVC elbow with the bird screen, at least 12 in. above expected snow.
  5. Intake pipe must be schedule 40 or 80 PVC, 3 in., max 80 ft total with each elbow counted as 10 ft.
  6. Reset the primary control per its data sheet and watch a full cycle.

Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Optional combustion air intake systems - CAP System, p.6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.