Carlin · Boiler troubleshooting
Checking the Carlin EZ ignitor
What is going on
Safe way to test the ignitor.
Likely causes
- Weak or no spark
Check in this order
- Never short the high voltage clips with a screwdriver.
- 40700 and 40900 ignitors only check by watching for spark at the electrodes with the oil supply OFF.
- 45000 ignitor power off, open the ignitor plate fully, set the high voltage clips to a 1/2 to 3/4 in. gap. Power on briefly. Spark jumping the gap = ignitor is good.
- Also check electrode gap and insulators per the electrode settings in the manual (p.10-11).
Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Maintenance procedures - Checking ignitor, p.17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.