Carlin · Boiler troubleshooting

Checking the Carlin EZ ignitor

Carlin EZ

What is going on

Safe way to test the ignitor.

Likely causes

  • Weak or no spark

Check in this order

  1. Never short the high voltage clips with a screwdriver.
  2. 40700 and 40900 ignitors only check by watching for spark at the electrodes with the oil supply OFF.
  3. 45000 ignitor power off, open the ignitor plate fully, set the high voltage clips to a 1/2 to 3/4 in. gap. Power on briefly. Spark jumping the gap = ignitor is good.
  4. Also check electrode gap and insulators per the electrode settings in the manual (p.10-11).

Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Maintenance procedures - Checking ignitor, p.17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.