Viessmann · Boiler troubleshooting

Heating circuit pump economy logic

Vitocrossal 300 CA3B

What is going on

Heating circuit pump switches off (supply set point 32°F (0°C)) when one of the following is met. Requires no frost risk and coding b0 set to 0.

Check in this order

  1. Outdoor temperature exceeds the value set in coding a5.
  2. Adjusted outdoor temperature exceeds the value set in coding a6.
  3. Mixing valve has tried to close for more than 12 min (coding a7).
  4. Pump idle time set in coding a9 has elapsed.
  5. Actual room temperature exceeds the value set in coding b5.
  6. If heating mode is restarted or set room temperature is raised during idle time, the pump starts immediately.

Applies to: Economy heating circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.