Viessmann · Boiler troubleshooting
Heating circuit pump economy logic
What is going on
Heating circuit pump switches off (supply set point 32°F (0°C)) when one of the following is met. Requires no frost risk and coding b0 set to 0.
Check in this order
- Outdoor temperature exceeds the value set in coding a5.
- Adjusted outdoor temperature exceeds the value set in coding a6.
- Mixing valve has tried to close for more than 12 min (coding a7).
- Pump idle time set in coding a9 has elapsed.
- Actual room temperature exceeds the value set in coding b5.
- If heating mode is restarted or set room temperature is raised during idle time, the pump starts immediately.
Applies to: Economy heating circuits
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.