Viessmann · Boiler troubleshooting

Wire circulation pumps to P1 and P2 by priority

Vitocrossal 200 CI2

What is going on

P1 and P2 have priority rules for DHW, heating circuit and recirculation pumps.

Check in this order

  1. P1 connect DHW pump first; if no DHW pump, use heating circuit pump for circuit without mixing valve.
  2. P2 connect heating circuit pump for circuit without mixing valve or circuits with mixing valve first.
  3. If no heating circuit A1 pump, connect DHW recirculation pump to P2.
  4. If a heating circuit pump without mixing valve is used, connect the DHW recirculation pump to the P1 extension (accessories).
  5. Connect standalone DHW recirculation pumps externally.

Applies to: P1 and P2 plugs

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.