External shut-off via terminal aBÖ (safety switch-off only)

Vitotronic 300

What is going on

A dry contact on terminal aBÖ gives a controlled switch-off. Use it only for safety switch-offs, such as a high limit thermostat.

Check in this order

  1. Remove the jumper between terminals 16 and 17.
  2. Connect the dry contact. Controlled switch-off happens when the contact opens.
  3. For emergency operation, move the jumper from terminals 16 and 17 to terminals 17 and 18.
  4. See page 52 for details of controlled switch-off.
  5. Warning during switch-off there is no frost protection for the heating system and the boiler is not held at minimum water temperature.

Applies to: VD2, VD2A, CT3 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.