Navien · Boiler troubleshooting
External recirculation with HotButton or aquastat and dedicated return
What is going on
Dedicated return DHW recirculation controlled either by a HotButton push button or by an aquastat, not both.
Check in this order
- For HotButton mode, install HotButton push button(s) and a recirculation pump, with no aquastat.
- For aquastat mode, install an aquastat and a recirculation pump, with no HotButton.
- For aquastat mode, connect the aquastat to terminal CNIN5 on the PCB.
- Set the aquastat below 140 °F (60 °C), the maximum DHW set temperature of the NCB700.
- HotButton push buttons and wall plates are sold separately.
Applies to: NCB700 DHW recirculation
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.