All brands · Boiler troubleshooting
No heat or some zones cold
What is going on
Boiler fires but a zone stays cold, or the boiler won't fire at all. Two different problems, so sort out which one you have first.
Likely causes
- Low system pressure, which also trips the low water cutoff on some boilers
- Air in the system, a zone airlocked and no flow
- Failed circulator pump or zone valve that will not open
- Thermostat or zone control wiring fault, so the call for heat never arrives
- Boiler in lockout
Check in this order
- Check the boiler display or LED for an error code, because a lockout needs the code, not guesswork
- Check system pressure (typically 12 to 20 psi cold on residential systems; confirm for the installation), low pressure means find the leak or fill
- Bleed air from radiators or purge the zone, because an airlocked zone gets no flow
- Confirm the circulator runs and the zone valve opens when the zone calls, feel the pipes and watch the valve end switch
- Check thermostat and zone control wiring, meter 24 V at the zone controller when the stat calls
- If the boiler is in lockout, reset once only and call a licensed tech if it comes back
Applies to: Hydronic boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.