Relief valve weeps every cycle / pressure climbs
What is going on
A relief valve that weeps every cycle or a pressure that keeps climbing is telling you the system can't absorb the water as it heats up. Nine times out of ten, it's the expansion tank. Don't plug or cap the relief valve, and let the system cool before working on it, since hot water can scald.
Likely causes
- Waterlogged or undersized expansion tank, which feels hot from top to bottom
- Pressure relief valve set too high
Check in this order
- Let the system cool and feel the tank, top and bottom should not both be hot
- Check the tank charge and recharge it, or replace the tank
- Recheck the cold fill pressure against the manual
- Watch the pressure as the boiler heats up
- Replace a weeping relief valve if it won't reseat after the tank is fixed
- Never plug the relief valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.