Condensing/corrosion of conventional boiler

What is going on

Flue gas is condensing inside a conventional boiler. It rots the heat exchanger and flue. Return water is too cold.

Likely causes

  • Return water under 140°F
  • No mixing valve to protect the boiler from cold return water
  • Oversized boiler cycling cold
  • Long low-temperature setback

Check in this order

  1. Measure the return water temperature.
  2. Add or adjust a mixing valve.
  3. Hold the return at about 140°F, with supply per the manufacturer.
  4. Inspect the exchanger and flue for corrosion.
  5. Check for dripping at the flue collar.
  6. Call a licensed tech to review the piping.

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.