Viessmann · Boiler troubleshooting
Fixed high limit test #2 (flow switch jumpered)
What is going on
Alternative test that trips the fixed high limit with the boiler valve closed and the flow switch jumpered. Only do this with the boiler monitored and under control.
Check in this order
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. For B2TB models, set coding address 06 to maximum to hold high fire.
- Let the temperature keep rising until the fixed high limit trips.
- Slowly open the boiler valve to cool the boiler down.
- Remove the jumper and restore normal operation.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.