Massachusetts venting: CO detectors and vent warning sign

SVF Series 1

What is going on

Applies to sidewall horizontally vented gas equipment where the vent termination is less than 7 feet above finished grade, in dwellings used for residential purposes.

Check in this order

  1. Confirm a hard-wired carbon monoxide detector with alarm and battery backup is installed on the floor level where the gas equipment is located.
  2. Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level of the building served.
  3. In a crawl space or attic installation, the detector may be installed on the next adjacent floor level.
  4. If the requirements cannot be met at completion, the owner has 30 days to comply, and a battery-operated CO detector with alarm must be installed during that time.
  5. Use CO detectors that comply with NFPA 720 and are ANSI/UL 2034 listed and IAS certified.
  6. Mount a metal or plastic sign on the building exterior at least 8 feet above grade, directly in line with the exhaust vent terminal. Lettering must be at least 1/2 inch and read: GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
  7. Leave all installation, venting and parts instructions with the appliance at completion.

Applies to: Sidewall horizontally vented gas equipment in Massachusetts

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.