Weil-McLain · Boiler troubleshooting
Massachusetts venting: CO detectors and vent warning sign
What is going on
Applies to sidewall horizontally vented gas equipment where the vent termination is less than 7 feet above finished grade, in dwellings used for residential purposes.
Check in this order
- Confirm a hard-wired carbon monoxide detector with alarm and battery backup is installed on the floor level where the gas equipment is located.
- Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level of the building served.
- In a crawl space or attic installation, the detector may be installed on the next adjacent floor level.
- If the requirements cannot be met at completion, the owner has 30 days to comply, and a battery-operated CO detector with alarm must be installed during that time.
- Use CO detectors that comply with NFPA 720 and are ANSI/UL 2034 listed and IAS certified.
- Mount a metal or plastic sign on the building exterior at least 8 feet above grade, directly in line with the exhaust vent terminal. Lettering must be at least 1/2 inch and read: GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
- Leave all installation, venting and parts instructions with the appliance at completion.
Applies to: Sidewall horizontally vented gas equipment in Massachusetts
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.